Smart Transmitter Power Supply Pepperl+Fuchs KFD2-STC4-EX1
KFD2-STC4-EX1,
KFD2-STC4-EX1.2O,
KFD2-EB2,
KFD2-EB2.R4A.B,
KCD2-SR-EX2,
KFD2-SRA-EX4,
KFD2-CD2-EX2,
KFD2-UT-EX1,
KFD2-STC4-EX1 KFD2-STC4-EX1.2O KFD2-EB2,
KCD0-SD-EX1.1245,
KFDO-SD2-EX1.1045,
KFD2-UT2-1,
KFD2-UT2-2,
KFD2-SCD-EX1.LK,
KFD2-STC5-EX1,
KFD2-STC4-EX1.20-Y1,
KFD2-VR2-EX1.50M,
KFD2-CD-EX1.32,
KFD2-STC5-EX2,
KFD2-STC5-EX1.20,
KFD2-STC4-1 KCD2-STC-EX1 OBD200-18GM60-E5-V1-IR-1C P+F,
KFD2-STC4-EX1-Y1,
KFD2-UT2-EX1,
KFD2-UT2-EX2,
KFD2-STC4-EX,
KFD2-SR2-EX1.W,
KFD2-SR2-EX2.W,
KFD2-SR2-EX1.WLB,
KFD2-CD-EX1.32,
KFD2-EB2.R2A.B,
KFD2-UFC-EX1.D,
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 14+, 15- | |
| Rated voltage | 20 … 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 1.4 W | |
| Power consumption | 1.8 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1+, 2-, 3 or 5-, 6+ | |
| Input signal | 0/4 … 20 mA | |
| Voltage drop | ≤ 2.4 V at 20 mA (terminals 5, 6) | |
| Input resistance | ≤ 64 Ω terminals 2-, 3 ; ≤ 500 Ω terminals 1+, 3 (250 Ω load) | |
| Available voltage | ≥ 16 V at 20 mA terminals 1+, 3 | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+, 9 | |
| Load | 0 … 800 Ω at 20 mA | |
| Output signal | 0/4 … 20 mA (overload > 25 mA) | |
| Ripple | max. 50 µA rms | |
| Transfer characteristics | ||
| Deviation | at 20 °C (68 °F), 0/4 … 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
|
| Influence of ambient temperature | 0.25 µA/K | |
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 … 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 … 7.5 kHz (-3 dB) |
|
| Settling time | 200 µs | |
| Rise time/fall time | 20 µs | |
| Galvanic isolation | ||
| Output/power supply | functional insulation, rated insulation voltage 50 V AC | |
| Indicators/settings | ||
| Display elements | LED | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529:2001 | |
| Protection against electrical shock | UL 61010-1:2012 | |
| Ambient conditions | ||
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |




Đánh giá